Three-Phase Power Calculator

Work out kW, kVA and kVAR for a balanced three-phase load, or the line current for a given power, with per-phase values for wye and delta.

Find
Voltage between any two phase conductors (208, 240, 400, 480, 600 …).
1 for heaters; induction motors at full load are typically 0.8–0.9.
Load connection
Real power (P)
35.33 kW47.38 hp equivalent
Line current
50 A
Apparent power (S)
41.57 kVA
Reactive power (Q)
21.9 kVAR
Phase angle
31.79°current lags voltage (inductive load assumed)
Per-phase voltage (wye)
277.1 V
Per-phase current (wye)
50 A
Power per phase
11.78 kW
Energy per hour
35.33 kWh
Real power35.33 kW41.57 kVA · 21.9 kVAR
  • Assumes a balanced load: equal impedance and current in all three phases. For unbalanced loads, add the three per-phase powers instead.
  • Calculations are for estimation only. Follow your local electrical code and have a licensed electrician design and install circuits.

Show the work

  1. P = √3 × VL × IL × PF = 1.7321 × 480 V × 50 A × 0.85 = 35.33 kW
  2. Apparent power S = √3 × VL × IL = 41.57 kVA
  3. Reactive power Q = √(S2 − P2) = 21.9 kVAR; phase angle φ = arccos(0.85) = 31.79°
  4. Wye: phase voltage = VL ÷ √3 = 277.1 V; phase current = line current = 50 A
P = 35.3 kWLoad: S = 41.6 kVA, Q = 21.9 kVAR, φ = 31.8°φQ

Three-phase power is how electricity is generated, transmitted and delivered to most commercial and industrial loads. Three alternating voltages, each a third of a cycle apart, deliver power smoothly and need less conductor material than single-phase for the same load. This calculator finds real, apparent and reactive power from line voltage, current and power factor — or the line current for a given kW — and breaks the result down per phase for wye and delta connections, with a power triangle drawn to scale.

How to use the three-phase power calculator

  1. Choose Power from volts & amps or Current from kW.
  2. Enter the line-to-line voltage, the voltage between any two phase conductors.
  3. Enter the line current or the real power in kW.
  4. Enter the power factor. Resistive heaters are 1; induction motors at full load are usually 0.8 to 0.9.
  5. Choose wye or delta to see the voltage and current in each phase of the load.

Three-phase power formulas

P = √3 × VL × IL × PF  ·  S = √3 × VL × IL  ·  Q = √(S2 − P2)
Wye: Vphase = VL ÷ √3, Iphase = IL  ·  Delta: Vphase = VL, Iphase = IL ÷ √3

P is real power in watts, S apparent power in volt-amperes and Q reactive power in VAR. The phase angle φ = arccos(PF) is the angle between voltage and current, and the angle at the corner of the power triangle.

Worked example

480 V, 50 A, power factor 0.85, wye (the default)

P = 1.7321 × 480 × 50 × 0.85 = 35.33 kW (about 47.4 hp).

S = 1.7321 × 480 × 50 = 41.57 kVA, and Q = √(41.57² − 35.33²) = 21.9 kVAR. The phase angle is arccos 0.85 = 31.79°.

Each wye phase sees 480 ÷ 1.732 = 277.1 V and carries 50 A, delivering 11.78 kW. In delta, each phase would see 480 V and carry 28.87 A.

Current from power. Switch to Current from kW and enter 35 kW: I = 35,000 ÷ (1.732 × 480 × 0.85) = 49.53 A.

Common three-phase voltages in North America

System Line-to-line Line-to-neutral Typical use
208Y/120 V 208 V 120 V Offices, retail, apartment buildings
240 V delta 240 V 120 V on two legs if high-leg Older shops and farms
480Y/277 V 480 V 277 V Industrial plants, large HVAC, lighting at 277 V
600Y/347 V 600 V 347 V Canadian industrial systems

Because current falls as voltage rises, the same 35 kW motor that draws about 50 A at 480 V would draw about 114 A at 208 V, needing much larger conductors.

Why three-phase is efficient

In a balanced three-phase system, the instantaneous power is constant instead of pulsing twice per cycle as it does in single-phase. Motors therefore run with steadier torque and less vibration, and three-phase motors start without the auxiliary windings or capacitors single-phase motors need. Three conductors carry √3 times the power of a single-phase pair at the same voltage and current — about 15% more power per conductor, which adds up to a real saving in copper on long feeders.

To size a transformer or generator in kVA, see the kVA calculator; to improve a low power factor, the power factor calculator. The voltage drop calculator checks long three-phase feeders.

Three-phase systems carry hazardous voltages and fault currents. These calculations are for estimation only; follow your local electrical code and have a licensed electrician perform all work.

Frequently asked questions

What is the formula for three-phase power?

P = √3 × VL × IL × PF, where VL is the line-to-line voltage, IL the line current and PF the power factor. At 480 V, 50 A and PF 0.85, P = 1.732 × 480 × 50 × 0.85 ≈ 35.3 kW.

Why is there a square root of 3 in three-phase formulas?

The three phase voltages are 120° apart, so the voltage between two lines is √3 times the voltage of one phase. Writing total power in terms of line voltage instead of phase voltage turns the factor of 3 (three phases) into √3.

What is the difference between wye and delta connections?

In a wye (star) connection each load sits between a line and neutral, so it sees VL ÷ √3 (277 V on a 480 V system) and carries the full line current. In a delta connection each load sits between two lines, so it sees the full line voltage but carries IL ÷ √3. Total power is the same either way.

How do I calculate three-phase current from kW?

I = P ÷ (√3 × VL × PF). A 35 kW load at 480 V and PF 0.85 draws 35,000 ÷ (1.732 × 480 × 0.85) ≈ 49.5 A per line.

What happens if the load is not balanced?

The √3 formula assumes equal current in all three phases. With unbalanced loads, calculate each phase separately as V(phase) × I × PF and add the three results. The neutral then carries the imbalance current in a wye system.

Last reviewed October 2026 by the CalcFluent editorial team. How we check our calculators.